Easton Din Rail Dual Display Adjustable Over Voltage Current and Under Voltage Protective Device Protector Relay 40Amp 230VAC (10006633)
Functions:
Over-voltage protection
Under-voltage protection
Over-current protection
Automatic recovery
Voltage display (voltage measurement)
Current display (current measurement)
Voltage calibration: Voltage +-10% adjustable. A13
Restore factory settings: press the down button for more than 12s
Fault inquiry: Press the UP button from more than 12S
Product Parameters:
2. Power supply:230VAC 50/60Hz
3. Max. Loading power:1~40A
4. Over-voltage protection value range:230V~300~OFF (default:270V)
Over-voltage recovery voltage range:225V--295V (default:250V)
Over-voltage protection action time:0.1s~30s (default value:0.5s)
Over-voltage recovery delay time:1s~500s (default:30s)
5. Under-voltage protection value range:140V--210V --OFF (default:170V)
Under-voltage recovery voltage range:145V--215V (default:190V)
Under-voltage protection action time:0.1s~30s (default:0.5s)
Under-voltage recovery delay time:1s~500s (default:30s)
6. Over-current adjustment range:1-40A (default:20A)
Over-current action range:0.1~30 second (default:0.5s)
Over-current recovery delay time:1s~500s (default:30s)
7. Power-on delay time:1s~500s (default:10s)
9. Power consumption : <2W
10. Electric machinery life : 100,000 times
11. Installation:35mm DIN rail
A14 Current limit times: 1-20 times (default off)
Restore factory settings: Press the down button for more than 12s
Fault inquiry: Press the UP button for more than 12S