| Main centres: | 1-3 business days |
| Regional areas: | 3-4 business days |
| Remote areas: | 3-5 business days |
Electrical Characteristics:
Rated voltage 1000VDC
Fuses available separately
Rated braking capacity 33kA dc
Minimum interrupting rating 1.3x In
Time constant under 1ms
Standard
IEC 60269-2
Technical Advice to Installers.
According to solar industry protection standards, two fuses are required: one for the positive pole and one for the negative pole.
To calculate the fuse rating, multiply the Amps of the PV string by x1.2.
Example PV String Amps: 11.5A x 1.2 = 13.8A. Nearest fuse 15A
PV String Fuses for solar panels gPV - 1000VDC
A range of fuses in a 10x38mm package specifically designed for protection and isolation of photovoltaic strings.
The DC fuses are capable of interrupting low overcurrent associated with faulted PV (reverse current, multi-array fault) string arrays.
Applications
Solar Panels, Solar Photovoltaic, DC Strings.