Main centres: | 1-3 business days |
Regional areas: | 3-4 business days |
Remote areas: | 3-5 business days |
Features
- True double-conversion online UPS
-Wide input voltage range (110-300 VAC)
-Input power factor correction 0.99
-Output power factor 0.8
-Converter mode available
-ECO mode operation for energy saving (only available for 1-3KVA)
-Generator compatible
-Adjustable battery numbers only available for 6K and up models
-Smart SNMP works well with either USB or RS-232 together
-Emergency power off function only available for 6K and up models
MODEL:ME-3000-WPTU
PHASE:Single phase with ground
CAPACITY:3000 VA / 2400 W
(with AVR,Monitoring Software + Cable & Built-in Surge Protection) - Black
INPUT
Voltage Range
Low Line Transfer:
-160 VAC/140 VAC/120 VAC/110 VAC ± 5% (Ambient Temp.<35°C)
-(based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
Low Line Comeback:
-175 VAC /155 VAC/ 135 VAC /125 VAC± 5 % (Ambient Temp.<35°C) (based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
-High Line Transfer:300 VAC ± 5 %
-High Line Comeback:290 VAC ± 5 %
-Frequency Range:40Hz ~ 70 Hz
-Power Factor:≧ 0.99 @ nominal voltage
OUTPUT
-Output Voltage:200/208/220/230/240 VAC
-AC Voltage Regulation (Batt. Mode):± 1%
-Frequency Range (Synchronized Range):47 ~ 53 Hz or 57 ~ 63 Hz
-Frequency Range (Batt. Mode):50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
-Current Crest Ratio:3:1
Transfer Time
-AC Mode to Batt. Mode:Zero
-Inverter to Bypass:4 ms (Typical)
-Waveform (Batt. Mode): Pure Sinewave
-Harmonic Distortion:≦ 3 % THD (Linear Load),≦ 6% THD (non-linear load)
EFFICIENCY
-AC Mode:90%
-Battery Mode:88%
BATTERY
-Battery Type:12 V / 9Ah
-Numbers:6
-Typical Recharge Time:4 hours recover to 90% capacity
-Charging Current (max.):1.0 A
-Charging Voltage:82.1 VDC ±1%
INDICATORS
-LCD Panel:UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
ALARM
-Battery Mode:Sounding every 4 seconds
-Low Battery:Sounding every second
-Overload:Sounding twice every second
-Fault:Continuously sounding
PHYSICAL
-Dimension, D x W x H (mm):421 x 190 x 318
-Net Weight (kgs):27.6
ENVIRONMENT
-Humidity:20-90 % RH @ 0- 40°C (non-condensing)
-Noise Level:Less than 50dB @ 1 Meter
MANAGEMENT
-Smart RS-232/USB:Supports Windows 2000/2003/XP/Vista/ 2008, Windows 7/8, Linux, Unix, and MAC
-Optional SNMP:Power management from SNMP manager and web browser
-NOTE 1: Derate to 80% of capacity in CVCF mode or when the output voltage is adjusted to 200/208VAC.
-NOTE 2: If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.