RCT 3000VA/2400W Online Rackmount UPS
RCT 3000VA/2400W Online Rackmount UPS. 12 V / 9 Ah batteries x6, Voltronic Power Winner Pro online pure sine wave UPS.
Specifications and features
Product CodeRCT-3000-WPRUspacer
CAPACITY3000 VA / 2400 W
PHASESingle phase with ground
INPUT
Input Voltage Range55-150 VAC or 110-300 VAC (Based on load at 50%); 85-140VAC or 160-280VAC (Based on load at 100%)
Nominal Voltage100/110/115/120/127VAC or 200/208/220/230/240VAC
Frequency Range40Hz ~70 Hz
Power Factor>= 0.99 @ Nominal Voltage (100% load)
OUTPUT
Voltage Regulation± 1%
Output Voltage100/110/115/120/127VAC or 200/208/220/230/240VAC
Frequency Range (Batt. Mode)50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz
Transfer Time : AC Mode to Battery ModeZero
Transfer Time : Inverter to Bypass4 ms (Typical)
Transfer Time : Waveform (Batt. Mode)Pure Sine Wave
Current Crest Ratio3::1
Harmonic Distortion
Frequency Range (Synchronized Range)47~53 Hz or 57~63 Hz
EFFICIENCY
Battery Mode0.88
AC Mode0.9
BATTERY
Long-run Model : Battery TypeDepending on the capacity of external batteries
Long-run Model : Charging Current (max.)1A/2A/4A/6A (Adjustable)
Long-run Model : Charging Voltage82.1 VDC ± 1% ,109.4 VDC ± 1%
Long-run Model : Numbers6, 8
Standard Model : Battery Type12 V / 9 AH
Standard Model : Charging Current (max.)1A
Standard Model : Charging Voltage82.1 VDC ± 1%
Standard Model : Numbers6
Standard Model : Typical Recharge Time4 hours recover to 90% capacity
INDICATORS
LCDLoad level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators
ALARM
Battery ModeSounding every 4 seconds
Low BatterySounding every second
OverloadSounding twice every second
FaultContinuously sounding
ENVIRONMENT
Operating Humidity20~90% RH @ 0- 40°C (non-condensing)
Noise LevelLess than 50dB @ 1 Meter
PHYSICAL
Standard Model : Dimension, D x W x H (mm)630 x 438 x 88 [2U]
Standard Model : Net Weight (kgs)29.3
Long-run Model : Dimension, D x W x H (mm)410 x 438 x 88 [2U]
Long-run Model : Net Weight (kgs)14.2
MANAGEMENT
Optional SNMPPower management from SNMP manager and web browser
Smart RS-232/USBSupports Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux, and MAC